The voltage regulator's primary function is to maintain a stable and precise generator voltage under no-load conditions and as loads fluctuate. When generators operate in parallel, a parallel compensation circuit is required to help voltage regulators manage reactive power distribution among the generators.
Reactive power imbalances between generators can occur when the voltage regulator adjusts the generator’s excitation due to load variations, prime mover speed changes, thermal drift, and other factors.
These excitation changes may lead to significant circulating currents flowing between generators (Drawing 20).
This results in the generator with higher field excitation attempting to supply power to the generator with lower field excitation, forcing it to match the output voltage of the more highly excited generator.
The parallel compensation circuit adjusts the voltage regulator by increasing the field excitation on the generator with lower excitation and decreasing it on the generator with higher excitation. By regulating the reactive load, this circuit effectively eliminates unwanted circulating currents.
An analogy for how one generator attempts to power another through circulating currents can be compared to two water pipes of equal diameter feeding into a single pipe. When both pipes have the same water pressure, they supply an equal amount of water to the common pipe (Drawing 21A). However, if one pipe experiences a slight drop in pressure, the second pipe will compensate by supplying more water to maintain the overall flow (Drawing 21B). Additionally, because the pressure in the second pipe is now higher than in the first, water will start flowing from the second pipe into the first in an attempt to equalize the pressure between them.
Reactive Droop Compensation and Reactive Differential Compensation
There are two primary types of parallel compensation circuits. The most commonly used method is parallel droop compensation, also known by its IEEE designation as reactive droop compensation. The second method is crosscurrent compensation, referred to in IEEE terminology as reactive differential compensation.
When reactive droop compensation is used to parallel two or more generators, each droop circuit operates independently (Drawing 22). A typical parallel droop circuit consists of a current transformer and a paralleling module. The module includes a burden resistor and a switch connected across the primary winding of a transformer (Drawing 23).
A switch in the paralleling module's transformer primary is used to short the secondary winding of the current transformer and the burden resistor, allowing the generator to operate independently of the paralleling system.
The secondary of the current transformer is connected to the paralleling circuit, where a burden resistor is placed across its output terminals (Drawing 24). The secondary current of the transformer induces a voltage across this resistor, which is then vectorially added to the line voltage to generate an error signal for the voltage regulator. The voltage across the burden resistor is directly proportional to the magnitude of the line current and maintains the same phase as the current flowing through the transformer's primary.
In a three-phase system, line-to-neutral voltages—regardless of internal connections—are displaced by 120 electrical degrees from one another. By leveraging this phase displacement, it is possible to sense system voltage from line to line, creating a line voltage that is shifted by 30 electrical degrees relative to the phase voltage. At unity power factor (resistive loads), the voltage signal from the current transformer’s burden resistor will be displaced by 90 electrical degrees from the system or line voltage (Drawing 26A).
At unity power factor, the vector diagram (Drawing 26B) shows that the burden resistor voltage (VB) and the sensing voltage (Vac) are 90 electrical degrees apart. When a reactive load is applied to the generator, the burden resistor voltage vector shifts either clockwise or counterclockwise, depending on the load type — capacitive or inductive.
If the generator operates with a leading power factor (capacitive load), the burden resistor voltage vector will rotate counterclockwise from its unity power factor position (Drawing 27). As a result, the phase angle between the line voltage and the burden resistor voltage increases, causing the regulator sensing voltage to decrease. This reduction in the sensing signal prompts the regulator to increase generator excitation.
When the generator operates with a lagging power factor (inductive load), the burden resistor voltage vector rotates clockwise from its unity power factor position (Drawing 28). This brings the phase angle between the line voltage and burden resistor voltage more in phase, increasing the voltage sensing signal to the regulator. In response to this larger signal, the regulator decreases generator excitation.
The paralleling module supplies an error signal to the voltage regulator, which controls the generator's excitation level. When generators are paralleled, the regulator detects this slight increase in sensing voltage and reduces excitation to the generator field, causing a voltage droop in the generator’s output.
The extent of voltage droop in a generator system can be adjusted using the burden resistor and the current transformer ratio. A typical burden resistor has a resistance of one ohm and features an adjustable slide tap to vary the voltage across it. The error signal sent to the voltage regulator depends on both the magnitude and vector angle of the voltage across the burden resistor. This voltage is determined by the secondary (output) current of the current transformer. Standard current transformers are designed for a 5-ampere secondary current with a 25VA maximum burden rating. According to Ohm’s Law (Voltage = Current × Resistance), the maximum voltage across a one-ohm burden resistor is 5 volts. This means that at full load, the voltage developed across the burden resistor is typically about 5% of the system’s output voltage (e.g., 120/208V, 240/416V, 480/600V) to minimize circulating currents.
When generators are paralleled with reactive droop compensation, most systems are set to operate at maximum droop. The burden resistor is adjusted for maximum resistance, ensuring maximum voltage across it. Operating at maximum droop allows for optimal control of circulating currents. If the system voltage droop is set to less than 3%, the regulator and paralleling circuit may struggle to effectively manage circulating currents.
Voltage regulators with single-phase sensing typically provide up to 8% maximum droop, whereas three-phase sensing regulators offer about 6% droop. Single-phase sensing results in greater droop because the average error signal is proportionally larger in comparison to the single-phase sensing voltage than to the three-phase sensing voltage. When paralleling generators on the same bus with different sensing types, adjustments to the burden resistor must be made to compensate for sensing differences.
- On Generator 1, the polarity-marked terminal of CT1 is connected to the non-polarity terminal of CT2 on Generator 2.
- On Generator 2, the polarity-marked terminal of CT2 is connected to the non-polarity terminal of CT1 on Generator 1.
- Automatic Voltage Regulators. What is a generator AVR or Automatic Voltage Regulator?
- Automatic Voltage Regulator and Parallel Operation of generators. Voltage droop
- Automatic Voltage Regulator. Real power, Reactive power, Apparent power. KW, KVAR, KVA
- Function of Voltage Regulator and Parallel Generator Operation
- The Current Transformer Unit - Parallel Switch. Paralleling Different Size Generators
- Checking and Troubleshooting a Reactive Compensation Circuit for the AVR in an Isolated AC Bus
- ACB Trouble. The generator does not connect to the main busbars. Troubleshooting
No comments:
Post a Comment